DPS 2900B-48-6 CellD 300 EVO (Orion controller)
Cabinet:
– Small Power System (5U), Subrack 19”, H222 x W444 x D315 mm, steel
– No Sliding mechanism included
AC-Connection:
– 3 phase mains connection 3L+N+PE; 230/400V
DC-Distribution:
– Max. space for 15x load breakers (2, 4, 6, 10, 16, 20. 25, 32, 40, 50, 63A; 1p); 15x MCB alarm card included (Load breaker supervision)
or
– Max. space for 7x load breakers (80, 100A; 2p)
or
– Max. space for 5x load breakers (120, 150A; 3p) *No breakers are included
Battery connection:
– Max. space for 6x 80-125A or 3x 160-200A or 2x 250-300A battery breakers *No breakers are included
– Battery Low Voltage Disconnection BLVD
Rectifier shelf:
– Space and cabling for 3x DPR 2900B-48 rectifier modules (nominal Power 8.7kW)
Power system controller:
– ORION ID: B1 power system controller