ORION Touch

SKU: ORION Touch CONTROLLER Category:

Description

Enhanced functions, such as efficiency mode and Genset fuel saving, enable operating cost reductions. Battery management with capacity test and lifetime prediction and enhanced rectifier functions including redundancy supervision make it easy to monitor system availability and plan site visits in cost effective manner. Remote monitoring and alarming, and consequent cost savings are ensured with potential-free relay contacts and modem or LAN/Ethernet, SMS, SNMP or Modbus. An integrated web server offers a user-friendly interface with a standard browser both for local and remote communication.

Additional Infomation

ORION ID: F1, known as ORIONc, has the the same functionality as ID:E1 but in a PSC 3 compatible physical format. It can be used to upgrade the functionality of old PSC 3 based systems to the latest level.

  • Orion ID E1 – TPS1020028A
  • Full functionality, all features

2017 update

  • Upgraded with touch panel
  • 1GB Lan connection -> IT network integration
  • New µC and more memory
  • 25% less power consumption
  • Micro SD slot -> simplified field service

 

Input
Mains voltage 18 – 60 VDC
Current 0.8ADC (Max.)
Protection / Switch Internal fuse 2A / None
General
Dimensions (W x H x D) 83.4 x 42.0 x 203.1mm (3.3 x 1.6 x 7.9 in)
Weight 0.6 kg (1.32 lb)
Standards
Safety EN / IEC 60950, class I; UL 60950; CAN / CSA-C22.2
EMC EN 55022, class B
Cooling Natural air flow
Operating temperature -40 to +70 °C (-40 to +158 °F)
Relative humidity 95%, non-condensing (Max.)
Function
System Site expansions using additional CAN based modules adding additional I/O’s and measurements
PLC functionality for customization and supervision and control of auxiliary devices
AC measurement, mains failure/phase failure detection and alarming Advanced Genset functions for fuel savings
Configurable event and data log/statistics
Remote and local SW and configuration update
 Battery Temperature compensated float charge, boost and equalise charge
Charging current limitation
Low voltage disconnection
State of charge supervision and display
Backup time supervision / Lifetime prediction
Automatic capacity test
Symmetry supervision for voltage and currents Block voltage supervision (optional) Lithium battery and combinations of Lithium and Lead Acid batteries
Block voltage supervision (optional)
Lithium battery and combinations of Lithium and Lead Acid batteries
Rectifier Individual rectifier information and control
Sequential start-up/system soft start
Efficiency mode with advanced rectifier cycling Redundancy and power capacity supervision
Redundancy and power capacity supervision