DPS Series 60-500 kVA

Three Phase

Delta’s Ultron DPS is a double-conversion and IGBT-rectifier three phase UPS.

DPS-300kva order number / bottom cable: GES304DS3312E35 VE UPS 300KVA I/O=220/380 Y 50HZ DPS2(DES)
(4 switches, Bottom cable entry )
DPS-400kva order number / bottom cable: GES404DS3312E35 VE UPS 400KVA I/O=220/380 Y 50HZ DPS2(DES)
(4 switches, Bottom cable entry)
DPS-500kva order number / bottom cable: GES504DS3312E35 VE UPS 500KVA I/O=220/380 Y 50HZ DPS2 WB
(4 switches, Bottom cable entry)
DPS-300kva order number / top cable: GES304DS3312F35 VE UPS 300KVA I/O=220/380 Y 50HZ DPS2(DES)
(4 switches,Top cable entry)

 

Download pdf pdf

Email for enquiry

Description

Delta’s Ultron DPS is a double-conversion and IGBT-rectifier three-phase UPS. With the three-level IGBT topology for both PFC (power factor correction) and inverter, the Ultron DPS features industry-leading performance of up to 96% AC-AC efficiency.

Model DPS-160K / DPS-200K / DPS-300K / DPS-400K / DPS-500K
Power Rating
[160K]
[200K]
[300K]
[400K]
[500K]
160kVA/144kW
200kVA/180kW
300kVA/270kW
400kVA/360kW
500kVA/450kW
Input
Nominal Voltage
Voltage range
Current Harmonic Distortion
Power Factor
Frequency
380/220, 400/230, 415/240 Vac (3 phase, 4-wire + G)
300~477 Vac (full load), 208~300 Vac (70%~100% load)
< 3%
> 0.99
45~65Hz
Output
Voltage
Output Power Factor
Voltage Harmonic Distortion
Voltage Regulation
Frequency
Overload Capability
380/220, 400/230, 415/240 Vac (3 phase, 4-wire + G)
0.9 (standard)
1 (optional) **
≤ 1.5% (linear load)
< 1% (linear load) **
± 1% (static)
50/60 ± 0.05 Hz
≦ 125%: 10 minutes